OpenADR 3, SunSpec Modbus and IEC 61850
Mental model
Section titled “Mental model”Energy integrations are layered. Devices such as inverters and batteries speak SunSpec Modbus at the edge, plants and substations speak IEC 61850, utilities send prices and limits to sites over OpenADR, and OPC UA or a gateway bridges between them. Before reading any spec, decide which layer your integration lives on — most confusion comes from expecting one protocol to do another layer’s job.
The layer map
Section titled “The layer map”| Layer | Protocol | You typically |
|---|---|---|
| Utility to site | OpenADR 3 | Consume events, post reports |
| Substation, plant | IEC 61850 | Read via a gateway |
| Plant SCADA, bridge | OPC UA | Browse a typed model |
| Device edge | SunSpec Modbus | Poll registers |
| Home appliances | Matter | Read energy clusters |
These are complementary, not competing. The OpenADR Alliance and the Connectivity Standards Alliance announced a liaison in May 2026 on exactly this split: Matter between appliance and home energy gateway, OpenADR 3 between that gateway and the utility. EV chargers add OCPP as their own device-to-backend link.
Utility BL -> VTN ==OpenADR 3==> site VENsite gateway ==SunSpec Modbus==> invertersite gateway ==Matter==> heat pumpModbus TCP essentials
Section titled “Modbus TCP essentials”| Function code | Operation |
|---|---|
0x03 | Read holding registers |
0x04 | Read input registers |
0x06 | Write single register |
0x10 | Write multiple registers |
Modbus TCP listens on port 502 by default. Each request carries a
7-byte MBAP header — transaction id, protocol id 0, length, unit id —
followed by the function code and data. A single 0x03 read returns 1
to 125 registers of 16 bits each, so large models need several reads.
import struct
def read_holding(tid, unit, addr, count): pdu = struct.pack(">BHH", 0x03, addr, count) mbap = struct.pack(">HHHB", tid, 0, len(pdu) + 1, unit) return mbap + pdu
print(read_holding(1, 1, 40000, 2).hex())# 00010000000601039c400002Note: The unit id replaces the serial slave address. A gateway uses it to route to the device behind it; for a device directly on TCP the Modbus guide recommends
0xFF, and0is also accepted.
SunSpec model chain
Section titled “SunSpec model chain”| Element | Value |
|---|---|
| Base address | 40000, else 0 or 50000 |
| Marker | Two registers spelling SunS |
| Model header | ID, then length L |
| Model 1 | Common: Mn, Md, SN |
| Model 103 | Three-phase inverter (legacy) |
| Model 701 | DER AC measurement (IEEE 1547) |
SunSpec turns raw Modbus into a self-describing map. After the SunS
marker, models follow back to back: each starts with its model ID
and its length L in registers, so a client walks the chain by
jumping L + 2 registers until it reads the end marker 0xFFFF. The
701–712 series replaces the 100 series for IEEE 1547-2018 devices.
regs = [0x5375, 0x6E53, # "SunS" 1, 2, 0, 0, # model 1, L=2 103, 1, 0, # model 103, L=1 0xFFFF, 0] # endi, models = 2, []while regs[i] != 0xFFFF: models.append(regs[i]) i += regs[i + 1] + 2print(models) # [1, 103]Gotcha: Device manuals often print 1-based register numbers (
40001) while clients send 0-based protocol addresses (40000). Off by one, you read the marker’s second half and find noSunS.
SunSpec scale factors and missing values
Section titled “SunSpec scale factors and missing values”| Type | Not implemented |
|---|---|
int16 | -32768 (0x8000) |
uint16, enum16 | 0xFFFF |
sunssf | -32768 |
acc32 | 0 |
Integer models store a value and a separate scale factor point, such
as W and W_SF: the real value is raw × 10^sf. Each type also has
a sentinel meaning “not implemented”, which a decoder must check
before scaling. Read the value and its scale factor in the same
request, so the pair always comes from one snapshot.
def scaled(raw, sf): if raw == -32768 or sf == -32768: return None # not implemented return raw * 10 ** sf
print(scaled(4521, -1)) # 452.1print(scaled(-32768, 0)) # NoneGotcha: The accumulator types use
0as “not implemented”, so a zero lifetime energy counter is ambiguous. Treat a counter that is zero on a producing device as missing, not as a reset.
OpenADR 3 resources
Section titled “OpenADR 3 resources”| Path | Written by | Holds |
|---|---|---|
/programs | BL | Business context, e.g. a tariff |
/events | BL | Prices or limits over intervals |
/reports | VEN | Usage or status for an event |
/subscriptions | VEN or BL | Webhook callbacks |
/vens, /resources | VEN or BL | Clients and their devices |
OpenADR 3 is a REST API. The VTN is the server; business logic
(BL, the utility side) and VENs (the customer side) are both its
clients, authenticated with OAuth 2.0 client credentials via
/auth/token. An event holds intervals, each with payloads whose
type (such as PRICE, SIMPLE or IMPORT_CAPACITY_LIMIT) is
explained by a matching payloadDescriptors entry.
{"programID": "1", "eventName": "tou-peak", "payloadDescriptors": [{ "objectType": "EVENT_PAYLOAD_DESCRIPTOR", "payloadType": "PRICE", "units": "KWH", "currency": "USD"}], "intervalPeriod": { "start": "2026-11-02T17:00:00Z", "duration": "PT1H"}, "intervals": [{"id": 0, "payloads": [ {"type": "PRICE", "values": [0.42]}]}]}OpenADR 3.1 notifications
Section titled “OpenADR 3.1 notifications”| Binding | Suits |
|---|---|
WEBHOOK | Cloud VENs that can accept inbound HTTP |
MQTT | VENs behind firewalls, e.g. in homes |
OpenADR 3.0 and 3.0.1 pushed changes only by webhook. 3.1.0, published
in 2025, adds MQTT so a VEN behind a home firewall can receive pushes
over a connection it opens itself. GET /notifiers lists the bindings
and the broker URIs; GET /notifiers/mqtt/topics/... returns the
topic name per operation. Each message is a notification with
objectType, operation and the full object.
{"topics": { "CREATE": "programs/create", "UPDATE": "programs/update", "DELETE": "programs/delete", "ALL": "programs/+"}}Gotcha: Topic names are chosen by each VTN and may be specific to your client. Always ask the topics endpoint; never hard-code the example strings above.
IEC 61850 orientation
Section titled “IEC 61850 orientation”| Part | Defines |
|---|---|
| 61850-6 | SCL, the XML configuration language |
| 61850-7-3 | Common data classes, e.g. MV |
| 61850-7-4 | Logical node classes |
| 61850-7-420 | DER logical nodes (ed. 2, 2021) |
| 61850-8-1 | Mapping to MMS over Ethernet |
IEC 61850 models a device as logical devices containing logical
nodes — four-letter classes such as MMXU (measurements), XCBR
(circuit breaker) or LLN0 (the logical device’s own node) — which
hold data objects and attributes. You rarely talk MMS yourself; a
gateway or OPC UA server exposes these names, and you need to read
them.
LD0/MMXU1.TotW.mag.f total active powerLD0/MMXU1.Hz.mag.f frequencyLD0/XCBR1.Pos.stVal breaker positionBridges: OPC UA and Matter
Section titled “Bridges: OPC UA and Matter”| Technology | Role in energy |
|---|---|
| OPC UA (IEC 62541) | Typed, browsable plant model |
| OPC UA for IEC 61850 | Companion spec mapping 61850 |
| Matter 1.4 | Home energy clusters and devices |
OPC UA exposes an address space of typed nodes that a client browses instead of memorising register maps, and the OPC Foundation’s IEC 61850 companion specification maps logical nodes into it. In homes, Matter 1.4 defines Electrical Power Measurement, Electrical Energy Measurement, Device Energy Management and Energy EVSE clusters, which a gateway can translate to OpenADR reports and limits.
inverter --Modbus--> gateway --OPC UA--> SCADAheat pump --Matter--> HEMS --OpenADR--> VTNTime and units traps
Section titled “Time and units traps”| Field | Rule |
|---|---|
OpenADR dateTime | RFC 3339, include the offset |
OpenADR duration | ISO 8601, e.g. PT15M |
PERCENT units | -1.0 to 1.0, not 0 to 100 |
P9999Y duration | May mean infinity |
0001-01-01 start | May mean now |
OpenADR timestamps carry their own offset and intervals are durations,
so 15-minute price intervals are PT15M from a stated start. Units
come from the payload descriptor (KW is power, KWH is energy), and
SunSpec values need their scale factor before any unit means anything.
from datetime import datetime, timedelta
start = datetime.fromisoformat( "2026-11-02T17:00:00-08:00")end = start + timedelta(minutes=15) # PT15Mprint(end.isoformat())# 2026-11-02T17:15:00-08:00Warning: OpenADR
PERCENT0.5 means 50%. Treating it as 0.5% sends devices a limit a hundred times too small, with no error.
Further reading