OpenADR 3.1.0

Energy integrations are layered. Devices such as inverters and batteries speak SunSpec Modbus at the edge, plants and substations speak IEC 61850, utilities send prices and limits to sites over OpenADR, and OPC UA or a gateway bridges between them. Before reading any spec, decide which layer your integration lives on — most confusion comes from expecting one protocol to do another layer’s job.

LayerProtocolYou typically
Utility to siteOpenADR 3Consume events, post reports
Substation, plantIEC 61850Read via a gateway
Plant SCADA, bridgeOPC UABrowse a typed model
Device edgeSunSpec ModbusPoll registers
Home appliancesMatterRead energy clusters

These are complementary, not competing. The OpenADR Alliance and the Connectivity Standards Alliance announced a liaison in May 2026 on exactly this split: Matter between appliance and home energy gateway, OpenADR 3 between that gateway and the utility. EV chargers add OCPP as their own device-to-backend link.

Utility BL -> VTN ==OpenADR 3==> site VEN
site gateway ==SunSpec Modbus==> inverter
site gateway ==Matter==> heat pump
Function codeOperation
0x03Read holding registers
0x04Read input registers
0x06Write single register
0x10Write multiple registers

Modbus TCP listens on port 502 by default. Each request carries a 7-byte MBAP header — transaction id, protocol id 0, length, unit id — followed by the function code and data. A single 0x03 read returns 1 to 125 registers of 16 bits each, so large models need several reads.

import struct
def read_holding(tid, unit, addr, count):
pdu = struct.pack(">BHH", 0x03, addr, count)
mbap = struct.pack(">HHHB", tid, 0,
len(pdu) + 1, unit)
return mbap + pdu
print(read_holding(1, 1, 40000, 2).hex())
# 00010000000601039c400002

Note: The unit id replaces the serial slave address. A gateway uses it to route to the device behind it; for a device directly on TCP the Modbus guide recommends 0xFF, and 0 is also accepted.

ElementValue
Base address40000, else 0 or 50000
MarkerTwo registers spelling SunS
Model headerID, then length L
Model 1Common: Mn, Md, SN
Model 103Three-phase inverter (legacy)
Model 701DER AC measurement (IEEE 1547)

SunSpec turns raw Modbus into a self-describing map. After the SunS marker, models follow back to back: each starts with its model ID and its length L in registers, so a client walks the chain by jumping L + 2 registers until it reads the end marker 0xFFFF. The 701–712 series replaces the 100 series for IEEE 1547-2018 devices.

regs = [0x5375, 0x6E53, # "SunS"
1, 2, 0, 0, # model 1, L=2
103, 1, 0, # model 103, L=1
0xFFFF, 0] # end
i, models = 2, []
while regs[i] != 0xFFFF:
models.append(regs[i])
i += regs[i + 1] + 2
print(models) # [1, 103]

Gotcha: Device manuals often print 1-based register numbers (40001) while clients send 0-based protocol addresses (40000). Off by one, you read the marker’s second half and find no SunS.

TypeNot implemented
int16-32768 (0x8000)
uint16, enum160xFFFF
sunssf-32768
acc320

Integer models store a value and a separate scale factor point, such as W and W_SF: the real value is raw × 10^sf. Each type also has a sentinel meaning “not implemented”, which a decoder must check before scaling. Read the value and its scale factor in the same request, so the pair always comes from one snapshot.

def scaled(raw, sf):
if raw == -32768 or sf == -32768:
return None # not implemented
return raw * 10 ** sf
print(scaled(4521, -1)) # 452.1
print(scaled(-32768, 0)) # None

Gotcha: The accumulator types use 0 as “not implemented”, so a zero lifetime energy counter is ambiguous. Treat a counter that is zero on a producing device as missing, not as a reset.

PathWritten byHolds
/programsBLBusiness context, e.g. a tariff
/eventsBLPrices or limits over intervals
/reportsVENUsage or status for an event
/subscriptionsVEN or BLWebhook callbacks
/vens, /resourcesVEN or BLClients and their devices

OpenADR 3 is a REST API. The VTN is the server; business logic (BL, the utility side) and VENs (the customer side) are both its clients, authenticated with OAuth 2.0 client credentials via /auth/token. An event holds intervals, each with payloads whose type (such as PRICE, SIMPLE or IMPORT_CAPACITY_LIMIT) is explained by a matching payloadDescriptors entry.

{"programID": "1", "eventName": "tou-peak",
"payloadDescriptors": [{
"objectType": "EVENT_PAYLOAD_DESCRIPTOR",
"payloadType": "PRICE",
"units": "KWH", "currency": "USD"}],
"intervalPeriod": {
"start": "2026-11-02T17:00:00Z",
"duration": "PT1H"},
"intervals": [{"id": 0, "payloads": [
{"type": "PRICE", "values": [0.42]}]}]}
BindingSuits
WEBHOOKCloud VENs that can accept inbound HTTP
MQTTVENs behind firewalls, e.g. in homes

OpenADR 3.0 and 3.0.1 pushed changes only by webhook. 3.1.0, published in 2025, adds MQTT so a VEN behind a home firewall can receive pushes over a connection it opens itself. GET /notifiers lists the bindings and the broker URIs; GET /notifiers/mqtt/topics/... returns the topic name per operation. Each message is a notification with objectType, operation and the full object.

{"topics": {
"CREATE": "programs/create",
"UPDATE": "programs/update",
"DELETE": "programs/delete",
"ALL": "programs/+"}}

Gotcha: Topic names are chosen by each VTN and may be specific to your client. Always ask the topics endpoint; never hard-code the example strings above.

PartDefines
61850-6SCL, the XML configuration language
61850-7-3Common data classes, e.g. MV
61850-7-4Logical node classes
61850-7-420DER logical nodes (ed. 2, 2021)
61850-8-1Mapping to MMS over Ethernet

IEC 61850 models a device as logical devices containing logical nodes — four-letter classes such as MMXU (measurements), XCBR (circuit breaker) or LLN0 (the logical device’s own node) — which hold data objects and attributes. You rarely talk MMS yourself; a gateway or OPC UA server exposes these names, and you need to read them.

LD0/MMXU1.TotW.mag.f total active power
LD0/MMXU1.Hz.mag.f frequency
LD0/XCBR1.Pos.stVal breaker position
TechnologyRole in energy
OPC UA (IEC 62541)Typed, browsable plant model
OPC UA for IEC 61850Companion spec mapping 61850
Matter 1.4Home energy clusters and devices

OPC UA exposes an address space of typed nodes that a client browses instead of memorising register maps, and the OPC Foundation’s IEC 61850 companion specification maps logical nodes into it. In homes, Matter 1.4 defines Electrical Power Measurement, Electrical Energy Measurement, Device Energy Management and Energy EVSE clusters, which a gateway can translate to OpenADR reports and limits.

inverter --Modbus--> gateway --OPC UA--> SCADA
heat pump --Matter--> HEMS --OpenADR--> VTN
FieldRule
OpenADR dateTimeRFC 3339, include the offset
OpenADR durationISO 8601, e.g. PT15M
PERCENT units-1.0 to 1.0, not 0 to 100
P9999Y durationMay mean infinity
0001-01-01 startMay mean now

OpenADR timestamps carry their own offset and intervals are durations, so 15-minute price intervals are PT15M from a stated start. Units come from the payload descriptor (KW is power, KWH is energy), and SunSpec values need their scale factor before any unit means anything.

from datetime import datetime, timedelta
start = datetime.fromisoformat(
"2026-11-02T17:00:00-08:00")
end = start + timedelta(minutes=15) # PT15M
print(end.isoformat())
# 2026-11-02T17:15:00-08:00

Warning: OpenADR PERCENT 0.5 means 50%. Treating it as 0.5% sends devices a limit a hundred times too small, with no error.